Dual Loop Module

Each Dual Loop Module provides control and connection of detection loop circuits for the Taktis Fire Alarm Control Panel.

All versions of the Panel must contain at least one Dual Loop Module. The Dual Loop Module monitors loop device status and communicates with the Panel processor. The Dual Loop Module can be connected in available Panel card slots on the main or extension board to provide operating functions. It holds device configurations and operates in a standalone manner if necessary. 

Main Features

  • Each card provides two monitored detection loops
  • Up to 4 modules can be installed to provide 8 detection loops on the standard Taktis Panel  
  • Up to 8 modules can be installed to provide 16 detection loops on the larger Taktis Panel  
  • Each Dual Loop Card can support either Hochiki or Apollo protocols. (Set by panel configuration) 
  • Simple ‘plug-in’ installation  
  • On board LED status indicators  
  • Loop card address set by DIP switch  Short circuit isolation onboard  
  • Autonomous device monitoring and basic fire reporting (fail safe) mode if the main panel display fails  
  • Provides up to 500mA detection loop current  
  • EN54-13 partial fault monitoring

Technical Documentation

Click to download the documents

Get in touch. We're here to help.

Contact us